Descripción del producto
Level sensors type T-20_.F... are approved by the DIBt (German Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Datos técnicos
Conexión
- ltdata.Polyesterdose
- PO/ET-520
- ltdata.Polyethylenanschlusskopf
- PE/ET-521
Propiedades
- Clase de protección EN60529
- IP 65
- Rosca de conexión
- G 1", G 1¼", G 1½", G2", G3”
- Tuerca de unión
- G 2¾", S 100x8
- Longitud del tubo guía
- max. 6 m
- Temperatura de funcionamiento
- max. 80 °C
- Presión de funcionamiento
- atmosphärisch
- Densidad del medio
- ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Histéresis de conmutación
- typ. 2 mm
- Tolerancia del punto de conmutación
- max. 2 mm
Fuente de alimentación
- Voltaje nominal
- 24 V DC (24…300V DC)
- Consumo de energía
- ≤ 1 W
Salidas
- Contacto de salida
- 1 potentialfreier Wechselkontakt
- Voltaje de conmutación
- max. 250 V AC / 30 V DC
- Corriente de conmutación
- max. 3 A AC / 3 A DC
- Capacidad de conmutación
- max. 750 VA / 90 W
Optoacoplador
- Voltaje de conmutación
- max. 30 V
- Corriente de conmutación
- max. 100 mA
- pantallas
- Betriebs-LED grün, Funktions-LED rot
- Retardo de conmutación
- ca. 0,5 s Anzug/Abfall
T200.F-24V Configurar
T20 - [ 1 ] - [ 2 ] - [ 3 ] - [ 4 ] - [ 5 ] - [ 6 ] - [ 7 ]
product description
- Funktionsbaugleich mit der Überfüllsicherung der Baureihe „T-20_.F..."
- Auswertung im Anschlusskopf/Dose
- Einfacher Aufbau
- Robuste Ausführung
- Geringe Abmessungen
- Niedrige Systemkosten
- Störsichere Messung
- Hohe chemische Beständigkeit
- Variabel einstellbarer Schaltpunkt (ohne zusätzliche Kontakte)
Das Ausgangsrelais arbeitet im Ruhestrombetrieb, d.h. im Alarmfall fällt das Ausgangsrelais ab in die Alarmstellung. Die Auswerteschaltung ist zusätzlich mit einem Halbleiterschalter (OptoKoppler) ausgerüstet (kleine Schaltströme (<20mA) z.B. SPS-Anlagen)
Red-Sensor | Leuchtdiode grün | Leuchtdiode rot | Schaltfunktion |
---|---|---|---|
≈ 1 kΩ | EIN | AUS | Betriebsbereit |
≈ 12 kΩ | EIN | EIN | Füll-Alarm |
< 1 kΩ | AUS | EIN | Kurzschluss-Alarm |
> 12 kΩ | AUS | EIN | L.-Unterbr.-Alarm |
- / - | AUS | AUS | Spannungs-Alarm |
Más información del producto
The floater switches the reed contact mounted in the guide tube when the liquid level rises. The change in resistance in the sensor circuit resulting from the switching operation is evaluated and the output relay triggered.
Parts of the level sensor which get into contact with the media are completely made of PE, PP, PVC, PVDF. So the level sensors T-20_.F... are perfectly suited for being used with tanks for storing highly aggressive media.
The overfill cut-out device consists of the level sensor and the measuring transducer. Our “contact protective relays” type KR-163... and KR-268..., which are also approved by the DIBt, can be used as corresponding measuring transducers (see section 10). The level sensors T-20_.F... can be connected to our “alarm indicators” type OAA-100 and OAA-300.
- Easy to install
- Sturdy design
- Small dimensions
- Interference-proof measurement
- Switching point adjustable
- Various options for connection (connector box / plug / cable)
- For usage in category 2 (Ex zone 1) (in combination with [Ex]i contact protective relay KR-163/A/Ex)
- Short-line fault / open circuit monitoring (in combination with contact protective relay KR-163... and KR-268... / alarm indicator OAA-100...)
- Under the F-contact further optional switching points can be realized
- Under the F-contact its also possible to integrate a continuous measurement
Documentos y descargas
Instrucciones de ajuste
Instrucciones de seguridad
Certificado de prueba
Vídeo sobre el producto
Accesorios

OAA-300
Ir al producto